298
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
■
H3-40: Mbus Reg 15C1h Input Function
No.
(Hex.)
Name
Description
Default
(Range)
H3-40
(0B5C)
Mbus Reg 15C1h Input
Function
Sets the MEMOBUS AI1 function.
F
(4 - 2E)
Uses the MFAI function from MEMOBUS/Modbus communications to set the input for the function in MEMOBUS/
Modbus register 15C1.
Refer to H3-xx "MFAI Setting Values" for the setting values.
■
H3-41: Mbus Reg 15C2h Input Function
No.
(Hex.)
Name
Description
Default
(Range)
H3-41
(0B5F)
Mbus Reg 15C2h Input
Function
Sets the MEMOBUS AI2 function.
F
(4 - 2E)
Uses the MFAI function from MEMOBUS/Modbus communications to set the input for the function in MEMOBUS/
Modbus register 15C2.
Refer to H3-xx "MFAI Setting Values" for the setting values.
■
H3-42: Mbus Reg 15C3h Input Function
No.
(Hex.)
Name
Description
Default
(Range)
H3-42
(0B62)
Mbus Reg 15C3h Input
Function
Sets the MEMOBUS AI3 function.
F
(4 - 2E)
Uses the MFAI function from MEMOBUS/Modbus communications to set the input for the function in MEMOBUS/
Modbus register 15C3.
Refer to H3-xx "MFAI Setting Values" for the setting values.
■
H3-43: Mbus Reg Inputs FilterTime Const
No.
(Hex.)
Name
Description
Default
(Range)
H3-43
(117F)
Mbus Reg Inputs FilterTime
Const
Sets the time constant to apply a primary delay filter to the MEMOBUS analog input register values.
0.00 s
(0.00 - 2.00 s)
◆
MFAI Setting Value
This section gives information about the functions set with
H3-02 and H3-10
.
■
0: Frequency Reference
Setting Value
Function
Description
0
Frequency Reference
The input value from the MFAI terminal set with this function becomes the master frequency reference.
•
You can copy the configuration to more than one of the analog input terminals A1 and A2. When you set more than
one analog input terminal with the master frequency reference, the sum value becomes the frequency bias.
•
If you use this function to set the analog input value as the master frequency reference, set
b1-01 = 1 [Frequency
Reference Selection 1 = Analog Input]
. This setting value is the default value for terminals A1 and A2.
•
The frequency reference is the sum of the input values for terminals A1 and A2 when you use them at the same
time. For example, when you input a 20% bias to terminal A2 and input a frequency reference of 50% from
terminal A1, the calculated frequency reference will be 70% of the maximum output frequency.
■
1: Frequency Gain
Setting Value
Function
Description
1
Frequency Gain
The drive multiplies the analog frequency reference with the input value from the MFAI set with this function.
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...