YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
673
No.
(Hex.)
Name
Description
MFAO Signal Level
U1-13
(004E)
Terminal A1 Level
Shows the signal level of terminal A1.
Unit: 0.1%
10 V = 100% (0 V to +10 V)
U1-14
(004F)
Terminal A2 Level
Shows the signal level of terminal A2.
Unit: 0.1%
10 V = 100% (0 V to +10 V)
U1-16
(0053)
SFS Output Frequency
Shows the output frequency after soft start. Shows the frequency with acceleration and deceleration
times and S-curves. Parameter
o1-03 [Keypad Display Unit Selection]
sets the display units.
Unit: 0.01 Hz
10 V = Maximum frequency
(0 V to +10 V)
U1-18
(0061)
oPE Fault Parameter
Shows the parameter number that caused the
oPE02 [Parameter Range Setting Error]
or
oPE08
[Parameter Selection Error]
.
No signal output available
U1-19
(0066)
MEMOBUS/Modbus Error
Code
Shows the contents of the MEMOBUS/Modbus communication error where 1 =
“
error
”
and 0 =
“
no
error
”
.
For example,
U1-19
shows
“
00000001
”
when there is a CRC error.
bit0 : CRC Error
bit1 : Data Length Error
bit2 : Not used (normal value of 0).
bit3 : Parity Error
bit4 : Overrun Error
bit5 : Framing Error
bit6 : Timed Out
bit7 : Not used (normal value of 0).
No signal output available
U1-25
(004D)
SoftwareNumber Flash
Shows the FLASH ID.
No signal output available
U1-26
(005B)
SoftwareNumber ROM
Shows the ROM ID.
No signal output available
U1-60
(1089)
System Setpoint
Shows the PID Setpoint.
Unit: 0.01%
Note:
Parameters
b5-46 [PID Unit Display Selection]
,
b5-38 [PID User Unit Display Scaling]
, and
b5-
39 [PID User Unit Display Digits]
set the unit, range, and resolution.
No signal output available
U1-61
(108A)
System Feedback
Shows the PID Feedback.
Unit: 0.01%
Note:
Parameters
b5-46 [PID Unit Display Selection]
,
b5-38 [PID User Unit Display Scaling]
, and
b5-
39 [PID User Unit Display Digits]
set the unit, range, and resolution.
No signal output available
U1-64
(108D)
Motor Speed
Shows the absolute value of the parameter
U1-02 [Output Frequency]
converted to RPM.
Unit: 1 RPM
No signal output available
U1-99
(3BAE)
Anti-No-Flow Timer
Shows the value of the anti-no-flow timer. When this value is at the
Y2-24 [Anti-No-Flow Detection
Time]
setting, the anti-no-flow feature starts to decrease the output frequency.
Unit: 0.1 s
No signal output available
◆
U2: Fault Trace
No.
(Hex.)
Name
Description
MFAO Signal Level
U2-01
(0080)
Current Fault
Shows the fault that the drive has when viewing the monitor.
No signal output available
U2-02
(0081)
Previous Fault
Shows the fault that occurred most recently.
No signal output available
U2-03
(0082)
Freq Reference@Fault
Shows the frequency reference at the fault that occurred most recently.
Use
U1-01 [Frequency Reference]
to monitor the frequency reference value.
Unit: 0.01 Hz
No signal output available
U2-04
(0083)
Output Freq @ Fault
Shows the output frequency at the fault that occurred most recently.
Use
U1-02 [Output Frequency]
to monitor the actual output frequency.
Unit: 0.01 Hz
No signal output available
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...