10.6 MEMOBUS/Modbus Communications
742
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Figure 10.22 Response Wait Time
◆
Message Format
■
Communication Message Description
In MEMOBUS/Modbus communications, the master sends commands to the slave, then the slave responds. The
master and slave send their messages in the configuration in
. The length of the data changes when the
description of the command (function) changes.
Figure 10.23 Message Format
■
Slave Address
Set the slave address of the drive to 01 to FF (Hex.).
Broadcast Messages
When the master broadcasts to a slave address of 00 (Hex), all slaves will receive the message. Slaves will provide no
response to a broadcast message.
■
Function Code
There are five function codes that set commands.
shows the different codes.
Table 10.21 Function Codes
Function Code
(Hex.)
Subfunction Code
(Hex.)
Function
Command Message
Response Message
Minimum Data
Length
(byte)
Maximum Data
Length
(byte)
Minimum Data
Length
(byte)
Maximum Data
Length
(byte)
03
-
Read Multiple Holding
Registers
8
8
7
37
08
-
Loopback Test
8
8
8
8
10
-
Writing to Multiple
Holding Registers
11
41
8
8
5A
-
Writing to Multiple
Holding Registers /
Reading the Register
Indicated
11
41
17
17
67
010D
Reading the Contents of
Non-Consecutive
Holding Registers
10
248
10
248
010E
Writing to Non-
Consecutive Holding
Registers
14
250
8
8
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...