636
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
L5-08
(0B2B)
Fault Reset Enable Select
Grp2
Use these 4 digits to set the Auto Restart function for
Uv1
,
ov
,
oH1
, and
GF
. From left to
right, the digits set
Uv1
,
ov
,
oH1
, and
GF
, in order.
0000 : Disabled
0001 : Enabled (—/–/—/GF)
0010 : Enabled (—/–/oH1/–)
0011 : Enabled (—/–/oH1/GF)
0100 : Enabled (—/ov/—/–)
0101 : Enabled (—/ov/—/GF)
0110 : Enabled (—/ov/oH1/–)
0111 : Enabled (—/ov/oH1/GF)
1000 : Enabled (Uv1/–/—/–)
1001 : Enabled (Uv1/–/—/GF)
1010 : Enabled (Uv1/–/oH1/–)
1011 : Enabled (Uv1/–/oH1/GF)
1100 : Enabled (Uv1/ov/—/–)
1101 : Enabled (Uv1/ov/—/GF)
1110 : Enabled (Uv1/ov/oH1/–)
1111 : Enabled (Uv1/ov/oH1/GF)
1111
(0000 - 1111)
L5-40
(3670)
Low Feedback Flt Retry
Selection
Sets the drive to do an Auto Restart when the drive detects an
LFB [Low Feedback
Sensed]
fault.
0 : No Retry
1 : Retry
0
(0, 1)
L5-41
(3671)
Hi Feedback Flt Retry
Selection
Sets the drive to do an Auto Restart when the drive detects an
HFB [High Feedback
Sensed]
fault.
0 : No Retry
1 : Retry
0
(0, 1)
L5-42
(3672)
Feedback Loss Fault
Retry Select
Sets the drive to try an Auto Restart when it drive detects an
FDBKL [WIRE Break]
fault.
0 : No Retry
1 : Retry
0
(0, 1)
L5-49
(3679)
Fault Retry Speed Search
Select
Sets the drive to do a speed search at the start of a Fault Retry.
0 : Disabled
1 : Enabled
1
(0, 1)
L5-50
(367A)
Setpoint Not Met Fault
Retry Sel
Sets the drive to try an Auto Restart when it detects an
NMS [SetPoint Not Met]
fault.
0 : No Retry
1 : Retry
0
(0, 1)
L5-51
(367B)
Loss of Prime Fault Retry
Select
Sets the drive to try an Auto Restart if it detects an
LOP [Loss Of Prime]
fault.
0 : No Retry
1 : Retry
0
(0, 1)
L5-53
(3251)
Thermostat Fault Retry
Selection
Sets the drive to try an Auto Restart if it detects a
VLTS [Thermostat Fault]
fault.
Note:
•
To use this function, set
S5-01 ≠ 0 [HAND Frequency Reference Source ≠ HAND
Analog Input]
•
The drive will only restart after the Thermostat digital input de-activates and the
L5-
04 [Interval Method Restart Time]
timer is expired.
0 : No Retry
1 : Retry
1
(0, 1)
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...