4.3 Start-up, Test Operation, and Rotation Check
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
129
12.
Switch any two phases on the
customer wiring side of the motor terminal block or motor overload
.
Note:
DO NOT change the wiring connected directly to the HV600 drive unit.
13.
Replace lower cover (or close cabinet door).
14.
Repeat Steps 1 to 8 of this procedure to confirm correct rotation in Drive Mode.
WARNING!
Sudden Movement Hazard. Before you do this step, remove all personnel and objects from the area around the
bypass and motor. The motor will rotate at full speed in this step and can cause serious injury or death.
15.
Push
to give the bypass a Run command from HAND Mode.
16.
Push
to show
S5-05 [HAND Frequency Reference]
.
17.
Push
to increase the frequency reference value.
Change the setting value in increments of 10 Hz if necessary and examine the response.
Each time you increase the setting value, use
U1-03 [Output Current]
to check the drive output current. Watch
and listen for unusual conditions or noises.
When the output current of the drive is not more than the motor rated current, the status is correct.
Example: 6 Hz → 20 Hz → 30 Hz → 40 Hz → 50 Hz → 60 Hz
18.
Set the HAND frequency reference back to the desired value, then push
. The test is complete.
■
Test Run and Rotation Check - Bypass Mode (HAND)
Before you do this procedure, Yaskawa strongly recommends that you do the items in
(including the Setup Wizard), and do the steps in
Test Run and Rotation Check - Drive
.
1.
Energize the bypass or push
to show the HOME screen.
2.
Push
to make sure that the bypass does not respond to an Auto-Run command.
3.
Check the lower-right corner of the keypad screen to make sure that the bypass is in Bypass Mode.
“BYPASS” will flash when the bypass is in Bypass Mode. If it is NOT in Bypass Mode, push
to put the
system into Bypass Mode
WARNING!
Sudden Movement Hazard. Before you do the next step, remove all personnel and objects from the area
around the bypass and motor. The motor will immediately rotate at full speed in the next step and can cause serious injury
or death.
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...