10 : MOTOR 1,2 in HAND AND/OR in AUTO
■
Z1-12: Run Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
Z1-12
(85D1)
Run Delay Time
Delays the drive or bypass Run from when commanded (after RUN, RUN ENABLE, and RUN
INTERLOCK are all asserted).
0.0 s
(0.0 to 300.0 s)
■
Z1-13: Pre Interlock Run Select
No.
(Hex.)
Name
Description
Default
(Range)
Z1-13
(85D2)
Pre Interlock Run Select
Lets the bypass run at a preset speed starting when it receives a Run command, and it ignores the
BAS Interlock Input. The drive frequency reference stays at this preset speed until
Z1-12 [Run Delay
Time]
is expired.
0
(0, 1)
0 : Disabled
1 : Enable time delay only
■
Z1-14: Run Delay Frequency Reference
No.
(Hex.)
Name
Description
Default
(Range)
Z1-14
(85D3)
Run Delay Frequency
Reference
Sets the frequency that the bypass uses when it delays the Run command.
60.00 Hz
(0.00 - Max. Freq.)
Note:
Actual values depend on unit settings of drive parameters
o1-03, o1-09, o1-10, and o1-11
.
■
Z1-15: Interlock Wait Time
No.
(Hex.)
Name
Description
Default
(Range)
Z1-15
(85D4)
Interlock Wait Time
When you enter a Run command, it asserts the damper actuator output. When you program an input
for Interlock and the time set to this parameter expires before the Interlock input activates, it will
trigger a fault.
0.0 s
(0.0 - 300.0 s)
Run Delay with Preset Speed Examples
Figure 5.99 Run Delay with Preset Speed Example: Default Settings
VFD RUN COMMAND
VFD OUTPUT FREQUENCY
DAMPER ACTUATOR OUTPUT
BAS INTERLOCK INPUT
t1
t2
t3
VFD FREQUENCY REFERENCE
Parameter Settings:
Z1-12 Run Delay Time = 0.0 sec
Z1-13 Pre Interlock Run Select = 0 (Disabled)
Z1-14 Run Delay Frequency Reference = 60.0 Hz
Z1-15 Interlck Wait Time = 0.0 sec (Never Time Out)
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...