656
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
9.15
T: Motor Tuning
◆
T0: Tuning Mode Selection
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
T0-00
(1197)
Tuning Mode Selection
Sets the type of Auto-Tuning.
0 : Motor Parameter Tuning
0
(0)
◆
T1: Induction Motor Auto-Tuning
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
T1-01
(0701)
Auto-Tuning Mode
Selection
Sets the type of Auto-Tuning.
0 : Rotational Auto-Tuning
2 : Stationary Line-Line Resistance
0
(0, 2)
T1-02
(0702)
Motor Rated Power
Uses the units set in
o1-58 [Motor Power Unit Selection]
to set the motor rated output
power.
Determined by o2-04
(0.00 - 650.00 HP)
T1-03
(0703)
Motor Rated Voltage
Sets the rated voltage (V) of the motor. Enter the base speed voltage for constant output
motors.
Determined by o2-04
(208/240 V: 0.0 - 255.5 V,
480 V: 0.0 - 511.0 V)
T1-04
(0704)
Motor Rated Current
Sets the rated current (A) of the motor.
Determined by o2-04
(10% to 200% of the
drive rated current)
T1-05
(0705)
Motor Base Frequency
Sets the base frequency (Hz) of the motor.
60.0 Hz
(0.0 - 400.0 Hz)
T1-06
(0706)
Number of Motor Poles
Sets the number of motor poles.
4
(2 to 120)
T1-07
(0707)
Motor Base Speed
Sets the motor base speed for Auto-Tuning (min
-1
(r/min)).
1750 min
-1
(r/min)
(0 - 24000 min
-1
(r/min))
T1-11
(070B)
Motor Iron Loss
Sets the iron loss for calculating the energy-saving coefficient.
Determined by E2-11
(0 - 65535 W)
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...