b4-07: Terminal M5-M6 ON-Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
b4-07
(0B34)
Expert
Terminal M5-M6 ON-Delay
Time
Sets the delay time to activate the contact after the function set in
H2-03
activates.
0 ms
(0 - 65000 ms)
■
b4-08: Terminal M5-M6 OFF-Delay Time
No.
(Hex.)
Name
Description
Default
(Range)
b4-08
(0B35)
Expert
Terminal M5-M6 OFF-Delay
Time
Sets the delay time to deactivate the contact after the function set in
H2-03
deactivates.
0 ms
(0 - 65000 ms)
◆
b5: PID Control
The drive has a PID control function. You can control drive output to adjust the proportional gain, integral time, and
derivative time that has an effect on the bias between the target value and the feedback value to align the target value
with the detected value. Use this function to adjust the drive output to accurately match the flow, pressure, and
temperature in the application match the target value.
Use a combination of these controls to increase the performance:
•
P control
P control has a proportional effect on the deviation. It outputs the product (the controlled output) proportional to the
deviation. You cannot use only the offset from P control to get to zero deviation.
•
I control
I control is the integral of the deviation. It uses an integral value of the deviation to output the product (the
controlled output). I control helps align the feedback value and the target value. If you use the proportional effect (P
Control) only, it will cause offset. If you use the proportional effect with the integral operation, it will gradually
remove the offset over time.
•
D control
D control is the derivative of the deviation. If there are sudden, large changes in the deviation or feedback value, it
will have an effect on drive output. It quickly returns drive output to the value before the sudden change. It
multiplies a time constant by a derivative value of the deviation (slope of the deviation), and adds that result to PID
input to calculate the deviation of the signal, then it corrects the deviation.
Note:
D control causes less stable operation because the noise changes the deviation signal. Use D control only when necessary.
■
PID Control Operation
shows PID control operation. The modified output (output frequency) changes when the drive uses PID
control to keep the deviation (the difference between the target value and the feedback value) constant.
Figure 5.22 PID Control Operation
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...