5.10 o: Keypad-Related Settings
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
371
No.
Item
Number of
Charac
ters
Example
Description
8
Sampling time
5
(maximum)
1000
Setting value (Dec.) of
o5-02 [Log Sampling Interval]
Unit: ms
9
Row number
6
000001
Row number (Hex.) in the data log file
*1
If you do not set the time in the keypad, the text string of [000000000000] is generated to show the time.
Second Row: Log Data Information
This example shows the data text strings and data generated for the second row of log data.
Example of generated data:
01,0012,160107111230,0101,0201,0102,0201,0103,0206,0107,0005,0108,0209,0000,0000,0000,0000,0000,0
000,0000,0000,0000,0000,0000,0000,0000,0000,000002
No.
Item
Number of
Characters
Description
1
Attribute
2
[01] shows that the record is a log data information record.
2
File number
4
The [xxx] part of the [GLOG0xxx.csv] filename is a 3-digit decimal number in hexadecimal format.
3
Time stamp
12
Date file was generated
4
Monitor number 1
4
Monitor number selected by
o5-03 [Log Monitor Data 1]
Ex.: 0101 (Dec.) for
U1-01
5
Monitor number 1
4
Unit code and number of decimal places used for the monitor selected with
o5-03
Example when
U1-01 = 30.00 Hz
:
Number of decimal places = 2, Hz unit code = 01, monitor unit 1 = 0201 (Hex.)
6
Monitor number 2
4
Monitor number selected by
o5-04 [Log Monitor Data 2]
7
Monitor number 2
4
Unit code and number of decimal places used for the monitor selected with
o5-04
:
:
:
:
22
Monitor number 10
4
Monitor number selected by
o5-12 [Log Monitor Data 1]
23
Monitor number 10
4
Unit code and number of decimal places used for the monitor selected with
o5-12
24 to 27
Reserved
4
-
28
File number
6
Row number (Hex.) in the data log file
*1
If there is no data log monitor selected, the text string of [0000] is generated.
*2
Refer to
for information about unit codes.
Table 5.53 Unit Codes
Unit Code (Hex.)
Unit
Unit Code (Hex.)
Unit
Unit Code (Hex.)
Unit
Unit Code (Hex.)
Unit
00
–
08
PPR
10
H
18
0H
01
Hz
09
kW
11
V
19
–
02
RPM
0A
Ω
12
us
1A
–
03
%
0B
ms
13
min
1B
–
04
VAC
0C
kHz
14
°C
1C
–
05
VDC
0D
PSI
15
W
1D
–
06
A
0E
MPM
16
kWH
1E
–
07
sec
0F
FPM
17
MWH
1F
–
Third and Subsequent Rows: Log Data
This example shows the data text strings and data generated for the third row of log data.
Example of generated data:
02,0012,160107111239,1770,1770,00BE,0118,0028,0000,0000,0000,0000,0000,0000,0000,00000C
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...