YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
327
Note:
•
If stall prevention during deceleration function causes
ov [Overvoltage]
and
Uv1 [DC Bus Undervoltage]
faults when you start deceleration
and
L3-04 = 2
, gradually increase this parameter in 0.1-unit increments. If the setting value is too high, it can cause large speed or current
ripples.
•
If sudden increases in the regenerative load cause
ov
faults and
L3-11
= 1, gradually increase this parameter in 0.1-unit increments. If the
setting value is too high, it can cause large speed or current ripples.
■
L3-21: OVSuppression Accel/Decel P Gain
No.
(Hex.)
Name
Description
Default
(Range)
L3-21
(0466)
Expert
OVSuppression Accel/Decel
P Gain
Sets the proportional gain to calculate acceleration and deceleration rates.
1.00
(0.10 - 10.00)
Set one of these parameters to enable
L3-21
:
•
L3-04 = 2 [Stall Prevention during Decel = Intelligent (Ignore Decel Ramp)]
•
L3-11 = 1 [Overvoltage Suppression Select = Enabled]
Note:
•
If stall prevention during deceleration function causes large speed or current ripples and
L3-04 = 2
, gradually decrease this parameter in
0.05-unit increments. If the drive detects
ov [Overvoltage]
or
oC [Overcurrent]
, decrease this parameter. If you decrease the gain too much,
it can cause a delay in control in the DC bus voltage or the deceleration time could be longer than the best deceleration time.
•
If sudden increases in the regenerative load cause
ov
faults and
L3-11 = 1
, gradually increase this parameter in 0.1-unit increments. If there
are large speed ripples, gradually decrease this parameter in 0.05-unit increments.
■
L3-23: Stall P Reduction at Constant HP
No.
(Hex.)
Name
Description
Default
(Range)
L3-23
(04FD)
Stall P Reduction at
Constant HP
Sets the function to automatically decrease the Stall Prevention Level during Run for constant output
ranges.
0
(0, 1)
0 : Use L3-06 for Entire Speed Range
The drive uses the level set in
L3-06 [Stall Prevent Level during Run]
through the full speed range.
1 : Automatic Reduction @ CHP Region
The drive decreases the Stall Prevention level during run in the constant power range. The lower limit is 40% of the
L3-06
value.
■
L3-24: Motor Accel Time @ Rated Torque
No.
(Hex.)
Name
Description
Default
(Range)
L3-24
(046E)
Expert
Motor Accel Time @ Rated
Torque
Sets the motor acceleration time to reach the maximum frequency at the motor rated torque for
stopped single-drive motors.
Determined by o2-04, E2-11
(0.001 - 10.000 s)
Set one of these parameters to enable
L3-24
:
•
L3-04 = 2 [Stall Prevention during Decel = Intelligent (Ignore Decel Ramp)]
•
L3-11 = 1 [Overvoltage Suppression Select = Enabled]
Note:
When Auto-Tuning changes the value of
E2-11 [Motor Rated Power]
, the drive will automatically set
L3-24
to the value for a Yaskawa
standard motor (4 poles).
Manually Adjust Parameters
Use this formula to find the motor acceleration time:
•
J
Motor
= Moment of inertia of motor (kg m
2
)
•
n
rated
= Motor rated speed (min
-1
, r/min)
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...