YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
281
L4-02: Speed Agree Detection Width
Figure 5.48 Speed Agree 1 Time Chart
ON : The output frequency is in the range of “frequency reference
±
L4-02
”.
OFF : The output frequency does not align with the frequency reference although the drive is
running.
■
3: User-Set Speed Agree 1
Setting Value
Function
Description
3
User-Set Speed Agree 1
The terminal activates when the output frequency is in the range of
L4-01 [Speed Agree Detection Level]
±
L4-02 [Speed Agree
Detection Width]
and in the range of the frequency reference ±
L4-02
.
Note:
The detection function operates in the two motor rotation directions. The drive uses the
L4-01
value as the forward/reverse detection level.
ON : The output frequency is in the range of “
L4-01
±
L4-02
” and the range of frequency reference
±
L4-02
.
OFF : The output frequency is not in the range of “
L4-01
±
L4-02
” or the range of frequency
reference
±
L4-02
.
L4-01: Speed Agree Detection Level
L4-02: Speed Agree Detection Width
Figure 5.49 User-Defined Speed Agree 1 Time Chart
■
4: Frequency Detection 1
Setting Value
Function
Description
4
Frequency Detection 1
The terminal deactivates when the output frequency >
“
L4-01 [Speed Agree Detection Level] + L4-02 [Speed Agree Detection
Width]
”
. After the terminal deactivates, the terminal stays deactivated until the output frequency is at the value of
L4-01
.
Note:
The detection function operates in the two motor rotation directions. The drive uses the
L4-01
value as the forward/reverse detection level.
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...