148
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Note:
Different settings and conditions will change the keypad display.
A -
o2-04 [Drive Model (KVA) Selection]
settings (2 or
3 digits)
B - Parameter backup data is not registered
C - Backup data does not contain the date
Information
D - Backup date
◆
Verify Keypad Parameters and Bypass Parameters
This procedure verifies that the parameter setting values that were backed up in the keypad agree with the parameter
setting values in the bypass.
Note:
•
Always stop the bypass before you start to verify the parameters.
•
The bypass will not accept a Run command while it verifies parameters.
1.
Push
(Home) to show the HOME screen.
Note:
• When the bypass is in HOME Mode, the screen shows [Home] in the upper right-hand corner of the screen.
• If the screen does not show [Home] for
, push
(Back), and then push
to show [Home].
2.
Push
(Menu).
3.
Push
or
to select [Parameter Backup/Restore], then push
.
4.
Push
or
to select the item to verify, then push
.
Back Home
#4 No Data
#3 ----/--/-- --:-- 0-65
#2 2020/01/01 02:10pm 0-65
#1 2020/01/01 14:10 0-65
Select Backup/Restore Location
10:00 am FWD Backup
A
D
C
B
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...