YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
403
bit 10 : VLTS - Thermostat Fault
bit 11 to 15 : Reserved
Note:
The drive sets the bits in Hex.
■
S6-16: EMOVR Customer Safety Mode
No.
(Hex.)
Name
Description
Default
(Range)
S6-16
(3247)
EMOVR Customer Safety
Mode
Sets the status for the customer safety input (when programmed) that must occur for Emergency
Override to function.
0
(0 - 2)
0 : Customer Safety Ignored
1 : EMOVRun Only When Safety OK
2 : EMOVRun Only When Safety NOT OK
Note:
You must set a customer safety to a Digital Input for this parameter to have an effect.
■
S6-17: EMOVR BAS Interlock Mode
No.
(Hex.)
Name
Description
Default
(Range)
S6-17
(3248)
EMOVR BAS Interlock
Mode
Sets the status for the BAS Interlock input (when programmed) that must occur for Emergency
Override to function.
0
(0 - 2)
0 : BAS Interlock Ignored
1 : EMOVRun Only When Interlock OK
2 : EMOVRun When Interlock NOT OK
Note:
Parameter has no effect if BAS Interlock is not programmed to a Digital Input.
■
S6-20: EMOVR Bypass Fault ON
No.
(Hex.)
Name
Description
Default
(Range)
S6-20
(324B)
Expert
EMOVR Bypass Fault ON
Enables bypass-specific faults.
0
(0 - FFFF)
0 : FB02
Wait For Interlock Timeout
1 : FB03
External Fault Bypass (EFB)
2 : FB05
Motor Overload
3 : FB06
External Overload 1
4 : FB07
External Overload 2
5 : FB08
Brownout Detected
6 : FB09
Blackout Detected
7 : FB10
Loss of Drive Communications
8 : FB13
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...