b5-53: PID Integrator Ramp Limit
No.
(Hex.)
Name
Description
Default
(Range)
b5-53
(0B8F)
RUN
PID Integrator Ramp Limit
Sets the responsiveness of PID control when the PID feedback changes quickly.
0.0 Hz
(0.0 - 10.0 Hz)
Note:
•
This parameter is disabled when set to 0.0 Hz.
•
When
b5-53 > 0.0 Hz
and the drive enables the integrator ramp limit, the PID integrator value limit is the range set by the output frequency
±
b5-53
.
•
When the PID feedback changes quickly, gradually decrease the this parameter in 0.1 Hz increments to decrease the speed of the response
of PID control.
■
b5-61: PID Trim Mode Lower Limit Sel
No.
(Hex.)
Name
Description
Default
(Range)
b5-61
(119A)
PID Trim Mode Lower Limit
Sel
Sets the function that adjusts the PID output in relation to the frequency reference.
0
(0, 1)
0 : Disabled
Does not adjust the PID output with the frequency reference.
1 : Enabled
Adjusts the PID output in relation to the frequency reference. The setting value of
b5-62 [PID Trim Mode Lower
Limit Value]
sets the lower limit of the post-adjustment value. The maximum output frequency sets the upper limit.
Note:
•
Set
b5-01 = 3 [PID Mode Setting = Fref + PID Trim]
to enable this parameter.
•
When
b5-61 = 1
, you can use this formula to adjust PID output proportional to the frequency reference:
U5-03 [PID Output]
,
Fref [Frequency Reference]
, and
Fmax [Maximum Output Frequency]
*1
Lower limit =
b5-62
, Upper limit = Maximum output frequency
■
b5-62: PID Trim Mode Lower Limit Value
No.
(Hex.)
Name
Description
Default
(Range)
b5-62
(119B)
PID Trim Mode Lower Limit
Value
Sets the PID Trim Mode Lower Limit Value as a percentage of the maximum output frequency.
0.00%
(0.00 - 100.00%)
Note:
Set
b5-01 = 3 [PID Mode Setting = Fref + PID Trim]
to enable this parameter.
■
b5-68: System Unit Custom Character 1
No.
(Hex.)
Name
Description
Default
(Range)
b5-68
(3C1F)
System Unit Custom
Character 1
Sets the first character of the custom unit display when
b5-46 = 49 [PID Unit Display Selection =
Custom (B5-68~70)]
.
41
(20 - 7A)
Refer to
for more information about available selections.
■
b5-69: System Unit Custom Character 2
No.
(Hex.)
Name
Description
Default
(Range)
b5-69
(3C20)
System Unit Custom
Character 2
Sets the second character of the custom unit display when
b5-46 = 49 [PID Unit Display Selection =
Custom (B5-68~70)]
.
41
(20 - 7A)
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...