111
This function allows a contact closure from a BAS, between terminals TB2-4 and TB2-10, to transfer motor operation
from Drive Mode to Bypass Mode. An open contact allows operation in Drive Mode and a closed contact allows
operation in Bypass Mode.
◆
Emergency Override
Terminal TB2-5 is a programmable input with a default setting of
“
Emergency Override
”
operation. Use
Z2-05
to
change the function of this terminal.
This function allows a contact closure between terminals TB2-5 and TB2-10 to transfer motor operation to bypass for
emergency override operation. The motor overload and Safety Interlock circuit are overridden during emergency
override or in emergency fire/smoke situations to place priority on personnel protection.
Note:
Emergency Override overrides all control inputs and bypass selector buttons. You must open the contact closure at terminal TB2-5 or open
the disconnect switch to terminate Emergency Override operation.
◆
Spare Multi-Function Digital Inputs
Terminals TB2-6, TB2-7, and TB2-8 are spare programmable inputs. The 24 V logic circuit is
interconnected with the drive multi-function digital inputs to allow a single customer interface to control both drive
and bypass circuits. The function of these terminals can be set using
Z2-06 and Z2-07
.
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...