YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
441
■
Z1-98: Minimum Drive SW Ver
No.
(Hex.)
Name
Description
Default
(Range)
Z1-98
(8627)
Expert
Minimum Drive SW Ver
“
WARNING: If these parameters are changed, undesired operation of the bypass system could occur.
These parameters should only be changed under guidance of Yaskawa technical support (1-800-
YASKAWA).
”
01011
00000 - 65535
■
Z1-99: Maximum Drive SW Ver
No.
(Hex.)
Name
Description
Default
(Range)
Z1-99
(8628)
Expert
Maximum Drive SW Ver
“
WARNING: If these parameters are changed, undesired operation of the bypass system could occur.
These parameters should only be changed under guidance of Yaskawa technical support (1-800-
YASKAWA).
”
01011
00000 - 65535
◆
Z2: Bypass Control Input/Output
■
Z2-01 to Z2-08 Digital Input 1 to 8 Function Selection
The drive has 8 digital input terminals. Refer to
for default settings and functions.
Table 5.70 Digital Input Default Settings and Functions
No.
Name
Default
Function
Z2-01
Digital Input 1 Function Select (TB2-1)
21
Run (AUTO)
Z2-02
Digital Input 2 Function Select (TB2-2)
22
Run Enable - Safety (NC)
Z2-03
Digital Input 3 Function Select (TB2-3)
23
Run Interlock (BAS)
Z2-04
Digital Input 4 Function Select (TB2-4)
24
Remote Transfer to Bypass
Z2-05
Digital Input 5 Function Select (TB2-5)
25
Emergency Override Bypass
Z2-06
Digital Input 6 Function Select (TB2-6)
0
Not Used
Z2-07
Digital Input 7 Function Select (TB2-7)
0
Not Used
Z2-08
Digital Input 8 Function Select (TB2-8)
0 or 29
Not Used or External Overload Motor 1 (NC)
Table 5.71 Digital Input Setting Values
Setting Value
Function
Reference
0
Not Used
1
Drive S1 Passthrough
2
Drive S2 Passthrough
3
Drive S3 Passthrough
4
Drive S4 Passthrough
5
Drive S5 Passthrough
6
Drive S6 Passthrough
7
Drive S7 Passthrough
21
Run (AUTO)
22
Run Enable - Safety (NC)
23
Run Interlock (BAS)
24
Remote Transfer to Bypass
25
Emergency Override Bypass
26
Emergency Override Drive (FWD)
27
Motor OR Select
28
Motor AND Select
Setting Value
Function
Reference
29
External Overload Motor 1 (NC)
30
External Overload Motor 2 (NC)
31
HAND Select
32
AUTO Select
33
Drive/Bypass Select
34
Fault Reset
35
External Fault (EF0)
36
External Fault (EFB)
37
Run Reverse (AUTO)
38
Fire Stat Switch (NC)
39
Freeze Stat Switch (NC)
40
Smoke Alarm (NC)
41
OverPressure Switch (NC)
42
Low Suction Switch (NC)
43
Vibration Switch (NC)
44
Emergency Override Drive (REV)
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...