670
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Setting Value
Function
Description
Ref.
6
READY
System ready.
7
RUN Active
Drive run or bypass run active.
8
Drive RUN active
The digital output activates when the system is in Drive Mode and the HV600 drive is running.
ON : Running in Drive Mode
OFF : Not running or in Bypass Mode
9
Bypass RUN active
The digital output activates when the system is in Bypass Mode and is running. Contactor K3 is closed.
ON : Running in Bypass Mode
OFF : Not running or in Drive Mode
10
HAND mode Active
The digital output activates when the system is running in HAND Mode during Drive Mode and Bypass Mode.
ON : Running in HAND Mode
OFF : Not running or in AUTO Mode
11
OFF mode Active
The digital output activates when the HAND/OFF/AUTO selection is in OFF Mode or if system is faulted. It is also
active when in Emergency Override Mode.
ON : System is in OFF Mode or is faulted
OFF : HAND Mode, AUTO Mode (even if not running), Emergency Override.
12
Auto mode Active
The digital output activates when the HAND/OFF/AUTO selection is in AUTO Mode. It will activate when the system
is running and when the system is not running and in Drive Mode and Bypass Mode.
ON : System is in AUTO Mode
OFF : HAND Mode, OFF Mode, Faulted, Emergency Override
13
Drive Mode Selected
The digital output activates when Drive Mode is selected. It stays active during Remote Transfer to Bypass,
Emergency Override Bypass, Energy Savings, Fault condition, and when the system is not running.
ON : Drive Mode is selected
OFF : Bypass Mode is selected
14
Bypass Mode Selected
The digital output activates when Bypass Mode is selected. It stays active during Emergency Override Drive, Fault
condition, and when the system is not running.
ON : Bypass Mode is selected
OFF : Drive Mode is selected
15
Fault Active
Set when there is an active Drive fault or Bypass fault.
16
Drive Fault Active
There is a fault in the HV600 drive.
17
Bypass Fault Active
There is a fault in the bypass.
18
Auto Transfer Active
There is a drive fault that activated Auto Transfer to Bypass.
19
Serial Run Active
Serial Communications is commanding a RUN.
20
Damper Actuator Output
System commanded to RUN in Drive Mode or Bypass Mode.
21
ON Always
This digital output is always active.
22
Loss of Load Detected
The motor current is less than the set value/values.
23
Run Verify Active
The digital output closes when the drive or bypass output current is more than 10% of
E2-01
.
The digital output opens when the drive or bypass output current is less than 5% of
E2-01
.
24
Soft Starter Run
Command
Controls the soft starter Run command to ramp down the soft starter before it opens bypass contactor K3.
25
Safeties Closed
All of the programmed safety digital inputs are satisfied.
26
Mirror HV600 M1-M2
The digital output activates when the HV600 drive digital output (M1-M2) is closed.
ON : Digital Output M1-M2 on HV600 is closed
OFF : Digital Output M1-M2 on HV600 is open
27
Mirror HV600 M3-M4
The digital output activates when the HV600 drive digital output (M3-M4) is closed.
ON : Digital Output M3-M4 on HV600 is closed
OFF : Digital Output M3-M4 on HV600 is open
28
Mirror HV600 M5-M6
The digital output activates when the HV600 drive digital output (M5-M6) is closed.
ON : Digital Output M5-M6 on HV600 is closed
OFF : Digital Output M5-M6 on HV600 is open
99
Not Used
This setting allows serial communications to control the output.
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...