YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
653
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
S6-04
(323B)
EMOVR Independent
PID Unit
Sets the units displayed for
S6-06 [EMOVR PID Setpoint]
when
S6-02 = 3 [Emergency
Override Ref Selection = Independent PID Mode]
.
0 :
“
WC: inches of water column
1 : PSI: pounds per square inch
2 : GPM: gallons/min
3 : °F: Fahrenheit
4 : ft
3
/min: cubic feet/min
5 : m
3
/h: cubic meters/hour
6 : L/h: liters/hour
7 : L/s: liters/sec
8 : bar: bar
9 : Pa: Pascal
10 : °C: Celsius
11 : m: meters
12 : ft: feet
13 : L/min: liters/min
14 : m
3
/min: cubic meters/min
15 :
“
Hg: Inch Mercury
16 : kPa: kilopascal
48 : %: Percent
49 : Custom(b5-68~70)
50 : None
48
(0 - 50)
S6-05
(323C)
EMOVR Independent
PID Unit Digit
Sets the number of digits for
S6-06 [EMOVR PID Setpoint]
when
S6-02 = 3[Emergency
Override Ref Selection = Independent PID Mode]
.
0 : No Decimal Places (XXXXX)
1 : One Decimal Places (XXXX.X)
2 : Two Decimal Places (XXX.XX)
3 : Three Decimal Places (XX.XXX)
2
(0 - 3)
S6-06
(323D)
RUN
EMOVR PID Setpoint
Sets the PID Setpoint when
S6-02 = 3[Emergency Override Ref Selection = Independent
PID Mode]
.
Note:
When
S6-02 = 3
: units and resolution are dependent on
S6-04 [EMOVR Independent
PID Unit]
and
S6-05 [EMOVR Independent PID Unit Digit]
. Value is internally
limited to 300% of
S6-03 [EMOVR Independent PID Scale]
.
0.00
(0 - 600.00)
S6-07
(323E)
EMOVR Fault
Suppression Mode
Sets the drive to let Emergency Override disable faults during operation.
0 : Fault Suppression
1 : Test Mode
0
(0, 1)
S6-08
(323F)
EMOVR Drive Enable
Input Mode
Sets whether the Drive Enable Input (if programmed) must be inactive (drive is disabled)
for Emergency Override to function.
0 : Drive Enable Status Ignored
1 : EMOVRun Only When Drive Disabled
Note:
You must program Drive Enable to a Digital Input for this parameter to have an effect.
0
(0, 1)
S6-09
(3240)
Emergency Override Min
Speed
When Emergency Override is active, the output frequency is lower-limited to this value.
0.00 Hz
(0.00 - 400.00 Hz)
S6-10
(3241)
Emergency Override Max
Speed
When Emergency Override is active, the output frequency is upper-limited to this value.
Note:
Set this parameter to 0.00 Hz to disable the limit.
0.00 Hz
(0.00 - 400.00)
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...