YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
449
4: K4 Motor 1 Contactor
Setting Value
Function
Description
4
K4 Motor 1 Contactor
Set when the K4 contactor is closed.
5: K5 Motor 2 Contactor
Setting Value
Function
Description
5
K5 Motor 2 Contactor
Set when the K5 contactor is closed.
6: READY
Setting Value
Function
Description
6
READY
System ready.
7: RUN Active
Setting Value
Function
Description
7
RUN Active
Drive run or bypass run active.
8: Drive RUN active
Setting Value
Function
Description
8
Drive RUN active
The digital output activates when the system is in Drive Mode and the HV600 drive is running.
ON : Running in Drive Mode
OFF : Not running or in Bypass Mode
Note:
This output stays active during Energy Savings Mode
Z1-16 = 1, 2 [Energy Savings Mode = Frequency, Fre Current
.
9: Bypass RUN active
Setting Value
Function
Description
9
Bypass RUN active
The digital output activates when the system is in Bypass Mode and is running. Contactor K3 is closed.
ON : Running in Bypass Mode
OFF : Not running or in Drive Mode
Note:
This output stays active during Energy Savings Mode
Z1-16 = 1, 2 [Energy Savings Mode = Frequency, Fre Current
.
10: HAND mode Active
Setting Value
Function
Description
10
HAND mode Active
The digital output activates when the system is running in HAND Mode during Drive Mode and Bypass Mode.
ON : Running in HAND Mode
OFF : Not running or in AUTO Mode
11: OFF mode Active
Setting Value
Function
Description
11
OFF mode Active
The digital output activates when the HAND/OFF/AUTO selection is in OFF Mode or if system is faulted. It is also active when in
Emergency Override Mode.
ON : System is in OFF Mode or is faulted
OFF : HAND Mode, AUTO Mode (even if not running), Emergency Override.
12: Auto mode Active
Setting Value
Function
Description
12
Auto mode Active
The digital output activates when the HAND/OFF/AUTO selection is in AUTO Mode. It will activate when the system is running
and when the system is not running and in Drive Mode and Bypass Mode.
ON : System is in AUTO Mode
OFF : HAND Mode, OFF Mode, Faulted, Emergency Override
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...