Offset Frequency 1 to 3]
to set the Offset frequency. When you close more than one input at the same time, the drive
adds the selected offset values together.
shows the Offset frequency function:
Figure 5.37 Offset Frequency Operation
■
d7-01: Offset Frequency 1
No.
(Hex.)
Name
Description
Default
(Range)
d7-01
(02B2)
RUN
Offset Frequency 1
Uses
H1-xx = 44 [MFDI Function Select = Add Offset Frequency 1 (d7-01)]
as a percentage of the
Maximum Output Frequency to add or subtract the set frequency to/from the frequency reference.
0.0%
(-100.0 - +100.0%)
■
d7-02: Offset Frequency 2
No.
(Hex.)
Name
Description
Default
(Range)
d7-02
(02B3)
RUN
Offset Frequency 2
Uses
H1-xx = 45 [MFDI Function Select = Add Offset Frequency 2 (d7-02)]
as a percentage of the
Maximum Output Frequency to add or subtract the set frequency to/from the frequency reference.
0.0%
(-100.0 - +100.0%)
■
d7-03: Offset Frequency 3
No.
(Hex.)
Name
Description
Default
(Range)
d7-03
(02B4)
RUN
Offset Frequency 3
Uses
H1-xx = 46 [MFDI Function Select = Add Offset Frequency 3 (d7-03)]
as a percentage of the
Maximum Output Frequency to add or subtract the set frequency to/from the frequency reference.
0.0%
(-100.0 - +100.0%)
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...