YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
703
Object ID
Object Name
(
Network Display, if
Different
)
Modbus Reg.
Precision
Range
Units
PV Access
AI8
Inverter Model o2-04
0508h
XXXXX
0-65535
-
R
AI9
Rated Current n9-01
05D0h
XXXX.X (for drives
rated higher than 11
kVA)
XXX.XX (for drives
rated 11 kVA or lower)
0-6553.5 (for drives
rated higher than 11
kVA)
0-65535 (for drives
rated 11 kVA or lower)
A
R
AI10
Motor Current UB-01
8780h
XXXX.X (for drives
rated higher than 11
kVA)
XXX.XX (for drives
rated 11 kVA or lower)
0-6553.5 (for drives
rated higher than 11
kVA)
0-65535 (for drives
rated 11 kVA or lower)
A
R
AI11
Contactor Voltage
8790h
XXXXX
0-65535
V
R
■
Analog Output Objects
Object ID
Object Name
(
Network Display
)
Modbus Reg.
Precision
Range
Units
PV Access
AO1
Drive Terminal FM
Analog Output Level
Command (set H4-01 =
0)
(
Drv Anlg Out1 Level
)
0007h
XXX.X
0-100.0
%
C
AO2
Drive Terminal AM
Analog Output Level
Command (Set H4-04 =
0)
(
Drv Anlg Out2 Level
)
0008h
XXX.X
0-100.0
%
C
■
Analog Value Objects
Object ID
Object Name
(
Network Display, if
Different
)
Modbus Reg.
Precision
Range
Units
PV Access
AV1
Drive Operation
Command
(Operation Cmd)
Note:
Do not command
bypass using AV1.
Use BV58 to BV71
instead.
0001h
-
0-65535
Bitmap
C
AV2
Frequency Cmd
0002h
XXX.XX
Determined by o1-03
0-600.00
Determined by o1-03
C
AV3
PI Setpoint Cmd
0006h
XXX.XX
0-100.00
%
C
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...