YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
605
9.6
C: Tuning
◆
C1: Accel & Decel Time
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
C1-01
(0200)
RUN
Acceleration Time 1
Sets the length of time to accelerate from zero to maximum output frequency.
30.0 s
(0.1 - 6000.0 s)
C1-02
(0201)
RUN
Deceleration Time 1
Sets the length of time to decelerate from maximum output frequency to zero.
30.0 s
(0.1 - 6000.0 s)
C1-03
(0202)
RUN
Acceleration Time 2
Sets the length of time to accelerate from zero to maximum output frequency.
30.0 s
(0.1 - 6000.0 s)
C1-04
(0203)
RUN
Deceleration Time 2
Sets the length of time to decelerate from maximum output frequency to zero.
30.0 s
(0.1 - 6000.0 s)
C1-09
(0208)
RUN
Fast Stop Time
Sets the length of time that the drive will decelerate to zero for a Fast Stop.
Note:
Decelerating too quickly can cause an
ov [Overvoltage]
fault that shuts off the drive
while the motor to coasts to a stop. Set a Fast Stop time in
C1-09
that prevents motor
coasting and makes sure that the motor stops quickly and safely.
10.0 s
(0.1 - 6000.0 s)
◆
C2: S-Curve Characteristics
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
C2-01
(020B)
S-Curve Time @ Start of
Accel
Sets the S-curve acceleration time at start.
0.20 s
(0.00 - 10.00 s)
C2-02
(020C)
S-Curve Time @ End of
Accel
Sets the S-curve acceleration time at completion.
0.20 s
(0.00 - 10.00 s)
C2-03
(020D)
S-Curve Time @ Start of
Decel
Sets the S-curve deceleration time at start.
0.20 s
(0.00 - 10.00 s)
C2-04
(020E)
S-Curve Time @ End of
Decel
Sets the S-curve deceleration time at completion.
0.00 s
(0.00 - 10.00 s)
◆
C3: Slip Compensation
No.
(Hex.)
Name
Description
Default
(Range)
Ref.
C3-01
(020F)
RUN
Slip Compensation Gain
Sets the gain for the slip compensation function. Usually it is not necessary to change this
setting.
Note:
Correctly set these parameters before you change the slip compensation gain:
•
E2-01 [Motor Rated Current (FLA)]
•
E2-02 [Motor Rated Slip]
•
E2-03 [Motor No-Load Current]
0.0
(0.0 - 2.5)
C3-02
(0210)
RUN
Slip Compensation Delay
Time
Sets the slip compensation delay time when speed is unstable or when the slip
compensation response is too slow. Usually it is not necessary to change this setting.
2000 ms
(0 - 10000 ms)
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...