420
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
You can also use
H1-xx = 83 to 85 [Dedicated Multi-Setpoint YA-02 to YA-04]
to select the digital setpoints as an
alternative to
3E
and
3F
.
shows which Setpoint is active as specified by the Dedicated Multi-Setpoint
Selections.
Table 5.68 Dedicated Multi-Setpoint Selections and Active Setpoints
Alternate Multi-Setpoint YA-02
H1-xx = 83
Alternate Multi-Setpoint YA-03
H1-xx = 84
Alternate Multi-Setpoint YA-04
H1-xx = 85
Setpoint
OFF
OFF
OFF
YA-01
ON
ON/OFF
ON/OFF
YA-02
OFF
ON
ON/OFF
YA-03
OFF
OFF
ON
YA-04
Note:
•
For all sources, you can change the value of setpoint with other functions, for example Sleep Boost function.
•
If you set a minimum of one PID Setpoint Selection (
H1-xx = 3E or 3F
) and a minimum one Alternate Multi-Setpoint Selection (
H1-xx =
83, 84, or 85
), the drive will detect an
oPE03 [Multi-Function Input Setting Err]
.
System Feedback Monitor
Monitor
U1-61 [System Feedback]
shows the currently set PID Feedback from these four sources:
•
H3-xx = B [MFAI Function Selection = PID Feedback]
•
H3-xx = 24 [PID Feedback Backup]
•
H3-xx= 2D [Differential Level Source]
Monitor
U1-61
will show the PID Feedback when the PID is disabled.
Note:
The System Feedback ignores these feedback sources, which are only shown in
U5-01 [PID Feedback]
:
•
MEMOBUS Register 15FF (Hex.) [Memobus PID Feedback]
•
H3-xx = 2B [Emergency Override PID Feedback]
•
MEMOBUS Register 3A95 (Hex.) [Emergency Override PID Feedback]
Automatic Setpoint Display Switch-over when in PID Mode
When the drive is in PID mode, the Home screen will change to show
U5-99 [Setpoint]
. It will not show
U1-01
[Frequency Reference]
.
When
b1-01 = 0 [Frequency Reference Selection 1 = Keypad]
and you push
on the Home screen, the keypad will
show
YA-01
,
YA-02
,
YA-03
, or
YA-04
and let you change it.
■
YA-01: Setpoint 1
No.
(Hex.)
Name
Description
Default
(Range)
YA-01
(3E58)
RUN
Setpoint 1
Sets the PID Setpoint when
b1-01 = 0 [Frequency Reference Selection 1 = Keypad or Multi-Speed
Selection]
.
0.00
(0.00 - 600.00)
Note:
Parameters
b5-46 [PID Unit Display Selection]
,
b5-38 [PID User Unit Display Scaling]
, and
b5-39 [PID User Unit Display Digits]
set the
unit, range, and resolution.
■
YA-02: Setpoint 2
No.
(Hex.)
Name
Description
Default
(Range)
YA-02
(3E59)
RUN
Setpoint 2
Sets the PID Setpoint as specified by the Multi-Setpoint digital inputs.
0.00
(0.00 - 600.00)
Note:
Parameters
b5-46 [PID Unit Display Selection]
,
b5-38 [PID User Unit Display Scaling]
, and
b5-39 [PID User Unit Display Digits]
set the
unit, range, and resolution.
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...