626
YASKAWA
SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference
Setting Value
Function
Description
Ref.
16A
!Data Logger Error
The terminal deactivates when the drive detects
LoG [Com Error / Abnormal SD card]
.
171
!Low PI2 Control
Feedback Level
The terminal deactivates when the PI2 Control Feedback Level is less than
S3-13 [PI2 Control Low Feedback Lvl]
.
172
!High PI2 Control
Feedback Level
The terminal deactivates when the PI2 Control Feedback Level is more than
S3-15 [PI2 Control High Feedback Lvl]
.
189
!Output Current Lim
The terminal deactivates when the output current limit is limiting the drive output speed.
194
!Loss of Prime
The terminal deactivates when the drive is in an
LOP [Loss of Prime]
condition.
195
!Thermostat Fault
The terminal deactivates when the terminal set for
H1-xx = 88 [MFDI Function Selection = Thermostat Fault]
is
active.
196
!High Feedback
The terminal deactivates when the drive is in a High Feedback Condition as specified by
Y1-11 [High Feedback Level]
and
Y1-12 [High Feedback Lvl Fault Dly Time]
and when the drive detects an
HFB [High Feedback Sensed]
fault or
an
HIFB [High Feedback Sensed]
alarm.
197
!Low Feedback
The terminal deactivates when the drive is in a Low Feedback Condition as specified by
Y1-08 [Low Feedback Level]
and
Y1-09 [Low Feedback Lvl Fault Dly Time]
and when the drive detects an
LFB [Low Feedback Sensed]
fault or an
LOFB [High Feedback Sensed]
alarm.
19E
!Low PI Auxiliary
Control Level
The terminal deactivates when the PI Aux Feedback Level is less than
YF-09 [PI Aux Control Low Level Detect]
or if
the drive detects an
LOAUX [Low PI Aux Feedback Level]
fault.
19F
!High PI Auxiliary
Control Level
The terminal deactivates when the PI Aux Feedback Level is more than
YF-12 [PI Aux Control High Level Detect]
or
if the drive detects an
HIAUX [High PI Aux Feedback Level]
fault.
1A9
!RELAY Operator
Control
The terminal changes to OFF or ON when you push the RELAY (
) button. When the terminal is ON, push
to turn it OFF. When the terminal is OFF, push
to turn in ON.
1AB
!Thrust Mode
The terminal deactivates when the output frequency is between 0.0 Hz and the value set in
Y4-12 [Thrust Frequency]
and the Thrust Bearing function is active.
1AC
!Setpoint Not Maintained
The terminal deactivates when the drive detects
NMS [Setpoint Not Met]
condition.
1B2
!BAS Interlock
The terminal deactivates when the Run command is active or the drive is outputting the voltage. The drive will use this
as an actuation signal for an external damper.
1B8
!Pump Fault
The terminal deactivates when one of these faults is active:
LFB [Low Feedback Sensed]
,
HFB [High Feedback
Sensed]
,
NMS [Setpoint Not Met]
, or
EFx [External Fault (Terminal Sx)]
.
1B9
!Transducer Loss
The terminal deactivates when the current into the analog input associated with PID feedback is more than 21 mA or
less than 3 mA, or an
FDBKL [WIRE Break]
Fault or an
FDBKL [Feedback Loss Wire Break]
Alarm is active.
1BA
!PI Auxiliary Control
Active
The terminal deactivates when the PI Auxiliary Controller has an effect on the output speed.
1BB
!Differential Feedback
Exceeded
The terminal deactivates when the difference between the PID Feedback and the value from the terminal set for
H3-xx
= 2D [Differential Feedback]
is more than
Y4-18 [Differential Level]
for the time set in
Y4-19 [Differential Lvl
Detection Time]
.
1BC
!Sleep Active
The terminal deactivates when the Sleep function is active and the drive is not operating.
Note:
The terminal will not deactivate for Sleep Boost function.
1BD
!Start Delay
The terminal deactivates when the Feedback is more than the start level or the Feedback is less than the Inverse PID
and the start timer is timing.
Note:
You must set
Y1-04 [Sleep Wake-up Level] ≠ 0
and
Y1-05 [Sleep Wake-up Level Delay Time] ≠ 0
to use this
function.
1BE
!Pre-Charge
The terminal deactivates when the drive is in Pre-Charge Mode.
1C0
!HAND Mode
The terminal deactivates when the drive is in HAND Mode operation.
1C1
!AUTO Mode
The terminal deactivates when the drive is in AUTO Mode operation.
1C2
!OFF Mode
The terminal deactivates when the drive is in OFF Mode operation.
1C3
!Main Feedback Lost
The terminal deactivates when the drive loses the main PID feedback.
1C4
!Backup Feedback Lost
The terminal deactivates when the drive loses the backup PID feedback.
Summary of Contents for H6B1A002
Page 12: ...12 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 74: ...Page Intentionally Blank...
Page 76: ...Page Intentionally Blank...
Page 454: ...5 14 Z Bypass Parameters 454 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 590: ...8 6 Storage Guidelines 590 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...
Page 780: ...11 3 European Standards 780 YASKAWA SIEPYAIH6B01A HV600 AC Drive Bypass Technical Reference...