p2215[0...n]
CO: Technology controller fixed value 15 / Tec_ctr fix val 15
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: DDS, p0180
Unit group: 9_1
Unit selection: p0595
Function diagram: 7950
Min:
-200.00 [%]
Max:
200.00 [%]
Factory setting:
150.00 [%]
Description:
Sets the value for fixed value 15 of the technology controller.
Dependency:
See also: p2220, p2221, p2222, p2223, r2224, r2229
NOTICE
A BICO interconnection to a parameter that belongs to a drive data set always acts on the effective data set.
p2216[0...n]
Technology controller fixed value selection method / Tec_ctr FixVal sel
Access level: 2
Calculated: -
Data type: Integer16
Can be changed: T
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 7950, 7951
Min:
1
Max:
2
Factory setting:
1
Description:
Sets the method to select the fixed setpoints.
Value:
1:
Direct selection
2:
Binary selection
p2220[0...n]
BI: Technology controller fixed value selection bit 0 / Tec_ctrl sel bit 0
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 7950, 7951
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source to select a fixed value of the technology controller.
Dependency:
See also: p2221, p2222, p2223
p2221[0...n]
BI: Technology controller fixed value selection bit 1 / Tec_ctrl sel bit 1
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 7950, 7951
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source to select a fixed value of the technology controller.
Dependency:
See also: p2220, p2222, p2223
p2222[0...n]
BI: Technology controller fixed value selection bit 2 / Tec_ctrl sel bit 2
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 7950, 7951
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source to select a fixed value of the technology controller.
Dependency:
See also: p2220, p2221, p2223