Connecting the cable shields, FSD ... FSG converters
The shield support for converter FSD is displayed as an example.
①
Unshielded line cable
④
Toothes tape
②
Shielded motor cable
⑤
Shielded control cable
③
Hose clamp
⑥
Unshielded communication cable
Note
Unshielded communcation cable
It is unnecessary to connect the cable shields if you use Siemens PROFINET cables for
communication. When using communication cables from other manufacturers, make sure that
you connect the cable shields with toothed tapes.
Note
Recommended connecters for PROFIBUS DP cable
We recommend Siemens connectors with the following article numbers for connecting the
PROFIBUS DP cable:
● 6GK1500-0FC10
● 6GK1500-0EA02
Wiring
4.1 Line supply and motor
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
97