p2247[0...n]
Technology controller motorized potentiometer ramp-up time / Tec_ctr mop t_r-up
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 7954
Min:
0.0 [s]
Max:
1000.0 [s]
Factory setting:
10.0 [s]
Description:
Sets the ramp-up time for the internal ramp-function generator for the motorized potentiometer of the technology
controller.
Dependency:
See also: p2248
Note
The time is referred to 100 %.
When the initial rounding-off is activated (p2230.2 = 1) the ramp-up is correspondingly extended.
p2248[0...n]
Technology controller motorized potentiometer ramp-down time / Tec_ctrMop t_rdown
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 7954
Min:
0.0 [s]
Max:
1000.0 [s]
Factory setting:
10.0 [s]
Description:
Sets the ramp-down time for the internal ramp-function generator for the motorized potentiometer of the technology
controller.
Dependency:
See also: p2247
Note
The time is referred to 100 %.
When the initial rounding-off is activated (p2230.2 = 1) the ramp-down is correspondingly extended.
r2250
CO: Technology controller motorized potentiometer setpoint after RFG / Tec_ctr mop aftRFG
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: PERCENT
Dynamic index: -
Unit group: 9_1
Unit selection: p0595
Function diagram: 7954
Min:
- [%]
Max:
- [%]
Factory setting:
- [%]
Description:
Displays the effective setpoint after the internal ramp-function generator for the motorized potentiometer of the
technology controller.
Dependency:
See also: r2245
p2251
Technology controller mode / Tec_ctrl mode
Access level: 3
Calculated: -
Data type: Integer16
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 7958
Min:
0
Max:
0
Factory setting:
0
Description:
Sets the mode for using the technology controller output.
Value:
0:
Technology controller as main speed setpoint
Dependency:
p2251 = 0 is only effective if the enable signal of the technology controller is interconnected (p2200 > 0).
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC