02
Forming completed
Yes
No
-
03
Forming fault
Yes
No
-
Dependency:
See also: p3380, r3381
See also: F07390, A07391
Note
For bit 00 = 1:
The parameter for activation/duration has been set (p3380 > 0) - however, forming has still not been started (p0840 =
0 signal).
For bit 01 = 1:
The parameter for activation/duration has been set (p3380 > 0) - however, forming has still not been started (p0840 =
0/1 signal).
This status is displayed through alarm A07391.
The procedure can be interrupted via binector input p0840, p0844, p0848 (r3382.1 = 0) - and reactivated again using
p0840.
For bit 03 = 1:
Forming was not able to be successfully performed within the set duration.
This status is displayed using fault F07390.
p3855[0...n]
DC quantity controller configuration / Rect_ctrl config
Access level: 3
Calculated:
CALC_MOD_LIM_REF
Data type: Unsigned32
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 6797, 6844,
6855
Min:
-
Max:
-
Factory setting:
0111 bin
Description:
Sets the configuration for the DC quantity controller in the overmodulation range.
There is no DC quantity control for power units that can also be connected through 1 phase to the line supply (r0204.15
= 1).
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
DC quantity controller on
Yes
No
-
01
Bandwidth increased
Yes
No
-
02
7th harmonic reduced
Yes
No
-
03
Filter active
Yes
No
-
Dependency:
The modulator mode p1802 must enable operation in the overmodulation range. In addition, the overmodulation limit
p1803 must be greater than 103 %.
Set the modulator mode p1802 = 10, if the DC quantity control is deactivated and overmodulation is to be prevented.
NOTICE
Motor identification must be carried out before activating the DC quantity control in the overmodulation range.
p3856[0...n]
Compound braking current / Compound I_brake
G120X_DP
(Compound brake),
G120X_PN
(Compound brake),
G120X_USS
(Compound brake)
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.00 [%]
Max:
250.00 [%]
Factory setting:
0.00 [%]
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
841