The diagram shows the layout of line and motor terminals and DC link terminals. For converter
FSH, you must make openings on the cable entry protection cover for the line and motor
connections according to the diameter of the cable to be introduced.
)6+
)6-
/LQHVXSSO\
0RWRU
/LQHVXSSO\
0RWRU
9
3(
8
9
:
8
'&1
'&3
:
3(
3(
3(
3(
3(
'&1
'&3
:
9
8
3(
:
8
9
3(
Figure 4-12
Connections for the line supply, motor and DC link terminals
Rules for connecting the line:
● Only use the front connections.
● You may connect 1 or 2 cables to each of the screws of the line connections.
Rules for connecting the motor:
● First use the front connections.
● If you use more than one cable per connection: Distribute the cables per connection evenly
on the left and right side of the connection.
● Only use the rear connections when the front connections are occupied.
After the cables are connected, you must re-attach the covers in order to re-establish the touch
protection of the converter (screw tightening torque: 6 Nm/53 lbf.in).
WARNING
Electric shock if the cable entry protection cover is not cut correctly
A cable entry protection cover which is not cut correctly may lead to dangerous touch voltage
which can result in serious injury or death.
● Make proper openings on the cover according to the required cable diameter in order to
ensure degree of protection IP20.
Wiring
4.1 Line supply and motor
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
93