p1023[0...n]
BI: Fixed speed setpoint selection Bit 3 / n_set_fixed Bit 3
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 2505, 3010,
3011
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source for selecting the fixed speed setpoint.
Dependency:
Selects the required fixed speed setpoint using p1020 ... p1023.
Displays the number of the actual fixed speed setpoint in r1197.
Sets the values for the fixed speed setpoints 1 ... 15 using p1001 ... p1015.
See also: p1020, p1021, p1022, r1197
Note
If a fixed speed setpoint has not been selected (p1020 ... p1023 = 0, r1197 = 0), then r1024 = 0 (setpoint = 0).
r1024
CO: Fixed speed setpoint effective / Speed fixed setp
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: -
Scaling: p2000
Dynamic index: -
Unit group: 3_1
Unit selection: p0505
Function diagram: 3001, 3010,
3011
Min:
- [rpm]
Max:
- [rpm]
Factory setting:
- [rpm]
Description:
Display and connector output for the selected and active fixed speed setpoint.
This setpoint is the output value for the fixed speed setpoints and must be appropriately interconnected (e.g. with the
main setpoint).
Recommendation:
Interconnect the signal with the main setpoint (CI: p1070 = r1024).
Dependency:
Selects the required fixed speed setpoint using p1020 ... p1023.
Displays the number of the actual fixed speed setpoint in r1197.
Sets the values for the fixed speed setpoints 1 ... 15 using p1001 ... p1015.
See also: p1070, r1197
Note
If a fixed speed setpoint has not been selected (p1020 ... p1023 = 0, r1197 = 0), then r1024 = 0 (setpoint = 0).
r1025.0
BO: Fixed speed setpoint status / n_setp_fix status
Access level: 3
Calculated: -
Data type: Unsigned8
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Display and binector output for the status when selecting the fixed speed setpoints.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Fixed speed setpoint selected
Yes
No
3011
Dependency:
See also: p1016
Note
For bit 00:
When the fixed speed setpoints are directly selected (p1016 = 1), this bit is set if at least 1 fixed speed setpoint is
selected.
Parameters
7.2 Parameter list
SINAMICS G120X converter
614
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC