NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1035[0...n]
BI: Motorized potentiometer setpoint raise / Mop raise
G120X_USS
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 2505, 3020
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source to continually increase the setpoint for the motorized potentiometer.
The setpoint change (CO: r1050) depends on the set ramp-up time (p1047) and the duration of the signal that is
present (BI: p1035).
Dependency:
See also: p1036
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1036[0...n]
BI: Motorized potentiometer lower setpoint / Mop lower
G120X_DP,
G120X_PN
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 2505, 3020
Min:
-
Max:
-
Factory setting:
[0] 2090.14
[1] 0
[2] 0
[3] 0
Description:
Sets the signal source to continuously lower the setpoint for the motorized potentiometer.
The setpoint change (CO: r1050) depends on the set ramp-down time (p1048) and the duration of the signal that is
present (BI: p1036).
Dependency:
See also: p1035
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.
p1036[0...n]
BI: Motorized potentiometer lower setpoint / Mop lower
G120X_USS
Access level: 3
Calculated: -
Data type: Unsigned32 / Binary
Can be changed: T
Scaling: -
Dynamic index: CDS, p0170
Unit group: -
Unit selection: -
Function diagram: 2505, 3020
Min:
-
Max:
-
Factory setting:
0
Description:
Sets the signal source to continuously lower the setpoint for the motorized potentiometer.
The setpoint change (CO: r1050) depends on the set ramp-down time (p1048) and the duration of the signal that is
present (BI: p1036).
Dependency:
See also: p1035
NOTICE
The parameter may be protected as a result of p0922 or p2079 and cannot be changed.