p1901
Test pulse evaluation configuration / Test puls config
G120X_DP (PM330),
G120X_PN (PM330),
G120X_USS (PM330)
Access level: 3
Calculated: CALC_MOD_ALL Data type: Unsigned32
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
0000 bin
Description:
Sets the configuration for the test pulse evaluation.
Bit 00: Check for conductor-to-conductor short circuit once/always when the pulses are enabled.
Bit 01: Check for ground fault once/always when the pulses are enabled.
Bit 02: Activation of the tests selected using bit 00 and/or bit 01 each time the pulses are enabled
Recommendation:
If the ground fault test is incorrectly initiated because the motor is not at a complete standstill, then the pulse
cancellation delay time (p1228) should be increased.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Phase short-circuit test pulse active
Yes
No
-
01
Ground fault detection test pulse active
Yes
No
-
02
Test pulse at each pulse enable
Yes
No
-
Dependency:
The ground fault test is only possible when the motor is stationary, and is therefore only realized when flying restart
is deactivated (p1200 = 0).
See also: p0287
Note
If a conductor-to-conductor short-circuit is detected during the test, this is displayed in r1902.1.
If a ground fault is detected during the test, this is displayed in r1902.2.
For bit 02 = 0:
If the test was successful once after POWER ON (see r1902.0), then it is not repeated.
For bit 02 = 1:
The test is not only performed after POWER ON, but also each time the pulses are enabled.
For chassis power units, the ground fault is also determined using the summed output current (see p0287).
r1902
Test pulse evaluation status / Test puls ev stat
Access level: 4
Calculated: -
Data type: Unsigned32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the status of the test pulse evaluation.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
Short-circuit test successfully performed
Yes
No
-
01
Phase short-circuit detected
Yes
No
-
02
Ground fault test successfully performed
Yes
No
-
03
Ground fault detected
Yes
No
-
04
Identification pulse width greater than the minimum pulse
width
Yes
No
-
05
Pulse frequency for short-circuit test requested
Yes
No
-
06
Short-circuit test in power stack driver activated
Yes
No
-
07
Short-circuit test pulse suppression active
Yes
No
-
08
Motor phase interrupted
Yes
No
-
Note
If the ground fault test was selected, but not successfully performed, then sufficient current was not be able to be
established during the test pulses.
For bit 04:
A test pulse longer than one sampling time has occurred
Parameters
7.2 Parameter list
SINAMICS G120X converter
720
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC