If the response is still not available, then you receive the following message via the present
value window of the OSV1:
Table 6-74
Read parameter content via OSV1
Byte
Description
2F h
00 h
0004 h
1
2
3,4
Function code 2F h (47)
Response length 0 (error)
Error code 4 h (response still not available)
If you wish to read the response once more, then you obtain the following message via the
present value window of the OSV1:
Table 6-75
Read parameter content again via OSV1
Byte
Description
2F h
00 h
0002 h
1
2
3,4
Function code 2F h (47)
response length 0 (error)
Error code 2 h (Invalid State)
Overview of the error codes
1 h: Invalid Length (invalid length)
2 h: Invalid State (action is not permitted in the actual converter state)
3 h: Invalid function Code (FC = 2 hex)
4 h: Response not ready (the response has still not been issued)
5 h: Internal Error (general system error)
Incorrect access operations to parameters via data set 47 are logged in objects OSV0 and
OSV1.
Advanced commissioning
6.3 Drive control
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
289