4. In the next steps of the quick commissioning, confirm all additional values that have already
been set.
5. Exit quick commissioning.
You have activated communication via Modbus RTU.
❒
ON/OFF commands via Modbus RTU
Selecting the macros 51 and 52 has the following effect:
● Only the ON/OFF2 command is possible via the terminal strip.
● The higher-level controller cannot turn the motor on or off.
To turn the motor on and off via the higher-level controller, you need to manually interconnect
the ON/OFF1 and OFF2 commands with the PROFIdrive control word:
● Set p0840[0] = r2090.0
● Set p0844[0] = r2090.1
Advanced commissioning
6.3 Drive control
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
243