Table 4-10
Overview of default settings, Part 2/2
Default setting (macro)
Terminal
48
49
51
1)
52
1)
54
1)
55
1)
57
3)
AI 0
-
-
-
Setpoint local
-
Setpoint local
-
AI 1
PID actual
value
PID actual
value
-
-
-
-
-
AO 0 Speed actual
value
Speed actual
value
Speed actual
value
Speed actual
value
Speed actual
value
Speed actual
value
Speed actual
value
AO 1
2)
Current ac‐
tual value
Current ac‐
tual value
Current ac‐
tual value
Current ac‐
tual value
Current ac‐
tual value
Current ac‐
tual value
Current ac‐
tual value
DI 0
ON/OFF2
ON/OFF2
ON/OFF2
ON/OFF2 lo‐
cal
ON/OFF2
ON/OFF2 lo‐
cal
Jogging 1
DI 1 Service pump
1
Service pump
1
-
ON/OFF2 re‐
mote
-
ON/OFF2 re‐
mote
Jogging 2
DI 2 Service pump
2
Service pump
2
-
-
-
-
-
DI 3
-
Service pump
3
-
-
-
-
-
DI 4 manual ↔ au‐
to
manual ↔ au‐
to
-
local ↔ remote
-
local ↔ remote local ↔ remote
DI 5 Acknowledge
fault
Acknowledge
fault
Acknowledge
fault
Acknowledge
fault
Acknowledge
fault
Acknowledge
fault
Acknowledge
fault
DO 0
Fault
Fault
Fault
Fault
Fault
Fault
Fault
DO 1
Operation
Pump 1
Operation
Operation
Operation
Operation
Operation
DO 2
2)
Pump 1
Pump 2
Ready for op‐
eration
Ready for op‐
eration
Ready for op‐
eration
Ready for op‐
eration
Ready for op‐
eration
DO 3
2)
Pump 2
Pump 3
Alarm
Alarm
Alarm
Alarm
Alarm
Fieldbus
-
-
Modbus RTU Modbus RTU
USS
USS
PROFINET
or PROFIBUS
1)
For converters with USS fieldbus interfaces
2)
With I/O Extension Module
3)
For converters with PROFIBUS or PROFINET interfaces
Function description
Default setting (macro) 41: "Analog control"
"Analog control" is the factory setting for converters with RS 485 fieldbus interfaces.
Wiring
4.2 Control interfaces
SINAMICS G120X converter
108
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC