Description:
Displays the motors which are interlocked/under repair.
Value:
r29544.0 = 1: Motor 1 is interlocked / under repair
r29544.1 = 1: Motor 2 is interlocked / under repair
r29544.2 = 1: Motor 3 is interlocked / under repair
r29544.3 = 1: Motor 4 is interlocked / under repair
r29544.4 = 1: Motor 5 is interlocked / under repair
r29544.5 = 1: Motor 6 is interlocked / under repair
Index:
[0] = Motor 1 under repair
[1] = Motor 2 under repair
[2] = Motor 3 under repair
[3] = Motor 4 under repair
[4] = Motor 5 under repair
[5] = Motor 6 under repair
r29545
CO/BO: Multi-pump control bypass command / Mpc bypass cmd
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the signal source for the control command to the bypass.It is BiCo to p1266.
Note
The "Bypass" function switches the motor between converter and line operation.
p29546
Multi-pump control deviation threshold / Mpc devia thres
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: PERCENT
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.00 [%]
Max:
100.00 [%]
Factory setting:
20.00 [%]
Description:
If the system deviation (p2273) at the PID technology controller exceeds the threshold (p29546) and no more motor
is available, alarm A52963 occurs.
p29547[0...5]
Multi-pump control continuous operating hours / Mpc Conti_oper_hrs
Access level: 3
Calculated: -
Data type: FloatingPoint32
Can be changed: T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.00 [h]
Max:
1000000.00 [h]
Factory setting:
0.00 [h]
Description:
Displays the continuous operating hours for the motors.
The display can only be reset to zero.
Index:
[0] = Motor 1 operating hours
[1] = Motor 2 operating hours
[2] = Motor 3 operating hours
[3] = Motor 4 operating hours
[4] = Motor 5 operating hours
[5] = Motor 6 operating hours
Note
Continuous operation is measured starting from when a motor is ON. It ends when a motor is OFF.
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
921