Function description
6,1$0,&6*;
)6$)6*
'212
'21&
'2&20
'212
'21&
'2&20
U
S
U
S
Figure 6-29
Feedback signal "STO is active" via digital outputs
For converters FSA…FSG, you must interconnect the feedback signals "STO is active" with
two digital outputs.
Procedure
1. Set p0730 = 1838.3
2. Set p0731 = 1838.4
You have interconnected the feedback signal for safety function STO with the digital outputs of
the converter.
❒
Parameters
Number
Name
Factory setting
p0730
BI: CU signal source for terminal DO 0
52.3
p0731
BI: CU signal source for terminal DO 1
52.7
r1838
CO/BO: Gating unit status word 1
.03 1 signal: Shutdown path STO_B is inactive
.04 1 signal: Shutdown path STO_A is inactive
---
Further information is provided in the parameter list.
Parameters (Page 467)
Advanced commissioning
6.3 Drive control
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
299