Note
Rounding-off times avoid an abrupt response and prevent damage to the mechanical system.
Rounding off is not active if the technology controller is used as main speed setpoint (p2251 = 0).
p1134[0...n]
Ramp-function generator rounding-off type / RFG round-off type
Access level: 2
Calculated: -
Data type: Integer16
Can be changed: T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 3070
Min:
0
Max:
1
Factory setting:
0
Description:
Sets the smoothed response to the OFF1 command or the reduced setpoint for the extended ramp-function generator.
Value:
0:
Continuous smoothing
1:
Discontinuous smoothing
Dependency:
No effect up to initial rounding-off time (p1130) > 0 s.
Note
p1134 = 0 (continuous smoothing)
If the setpoint is reduced while ramping-up, initially a final rounding-off is carried out and then the ramp-up completed.
During the final rounding-off, the output of the ramp-function generator continues to go in the direction of the previous
setpoint (overshoot). After the final rounding-off has been completed, the output goes toward the new setpoint.
p1134 = 1 (discontinuous smoothing)
If the setpoint is reduced while ramping-up, then the output goes immediately in the direction of the new setpoint. For
the setpoint change there is no rounding-off.
p1135[0...n]
OFF3 ramp-down time / OFF3 t_RD
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: C2(1), T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 3070
Min:
0.000 [s]
Max:
5400.000 [s]
Factory setting:
0.000 [s]
Description:
Sets the ramp-down time from the maximum speed down to zero speed for the OFF3 command.
Note
This time can be exceeded if the DC link voltage reaches its maximum value.
p1135[0...n]
OFF3 ramp-down time / OFF3 t_RD
G120X_DP (PM330),
G120X_PN (PM330),
G120X_USS (PM330)
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: C2(1), T, U
Scaling: -
Dynamic index: DDS, p0180
Unit group: -
Unit selection: -
Function diagram: 3070
Min:
0.000 [s]
Max:
5400.000 [s]
Factory setting:
3.000 [s]
Description:
Sets the ramp-down time from the maximum speed down to zero speed for the OFF3 command.
Dependency:
The parameter is pre-assigned depending on the size of the power unit.
Note
This time can be exceeded if the DC link voltage reaches its maximum value.