p0230
Drive filter type motor side / Drv filt type mot
G120X_DP (PM330),
G120X_PN (PM330),
G120X_USS (PM330)
Access level: 1
Calculated: -
Data type: Integer16
Can be changed: C2(1, 2)
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
2
Factory setting:
0
Description:
Sets the type of the filter at the motor side.
Value:
0:
No filter
1:
Motor reactor
2:
dv/dt filter
Dependency:
The following parameters are influenced using p0230:
p0230 = 1:
--> p0233 (power unit, motor reactor) = filter inductance
See also: p0233, p0234, p0290, p1082, p1800, p1802
Note
If a filter type cannot be selected, then this filter type is not permitted for the power unit.
p0230 = 1:
Power units with output reactor are limited to output frequencies of 150 Hz.
r0231[0...1]
Power cable length maximum / Cable length max
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
- [m]
Max:
- [m]
Factory setting:
- [m]
Description:
Displays the maximum permissible cable lengths between the drive unit and motor.
Index:
[0] = Unshielded
[1] = Shielded
Note
The display value is used to provide information for service and maintenance.
p0233
Power unit motor reactor / PU mot reactor
Access level: 2
Calculated: -
Data type: FloatingPoint32
Can be changed: C2(1), T, U
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0.000 [mH]
Max:
1000.000 [mH]
Factory setting:
0.000 [mH]
Description:
Enter the inductance of a filter connected at the power unit output.
Dependency:
This parameter is automatically pre-set when you select a filter via p0230 if a SIEMENS filter is defined for the power
unit.
See also: p0230
Note
When exiting the quick commissioning using p3900 = 1, the parameter value is set to the value of the defined SIEMENS
filter or to zero. For this reason, the parameter value of a third-party filter only has to be entered outside the
commissioning phase (p0010 = 0) and then the controller calculation (p0340 = 3) is carried out.
The parameter cannot be changed if the power unit (e.g. PM260) is equipped with an internal sine-wave filter.
Parameters
7.2 Parameter list
SINAMICS G120X converter
506
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC