4.1.1.3
IT system
Overview
7UDQVIHURI1LPSHGDQFHZLWK
UHVSHFWWR3(SURWHFWLYHFRQGXFWRU
7UDQVIRUPHURU
JHQHUDWRU
7RWKHV\VWHP
([DPSOH
/
/
/
1
3(
Figure 4-3
IT system
In an IT system, all of the conductors are insulated with respect to the PE protective conductor
– or connected to the PE protective conductor through an impedance.
There are IT systems with and without transfer of the neutral conductor N.
Function description
Table 4-3
Converter operated on an IT system
Converter
Line supply with grounded neutral
Line supply with grounded phase conduc‐
tor and a voltage ≤ 600 V phase to phase
Frame size
A
B
C
D
E
F
G
H
J
A
B
C
D
E
F
G
H
J
Without line
filter
✓
✓
✓
✓
✓
✓
○
○
○
✓
✓
✓
✓
✓
✓
○
○
○
Integrated
line filter C2
-
-
-
-
-
-
-
○
○
-
-
-
-
-
-
-
○
○
Integrated
line filter C3
○
○
○
○
○
-
✓
1)
✓
1)
✓
1)
○
○
○
○
○
-
✓
1)
✓
1)
✓
1)
✓ = Operation permissible
✓
1)
Operation permissible once grounding screw has been removed
If the grounding screw has been removed, the converter no longer fulfills the requirements of class C3.
- Operation not permissible
○ Converter not available
More information on removing the grounding connection in the converter:
Removing functional grounding of the converter (Page 78)
4.1.1.4
Removing functional grounding of the converter
If you wish to use the converters with C2/C3 line filter, note the information in the following
sections:
Wiring
4.1 Line supply and motor
SINAMICS G120X converter
78
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC