Procedure for converters in frame sizes FSD ... FSG
&RQQHFWLRQ$IRUVHOHFWLRQRI672
&RQQHFWLRQ%IRUVHOHFWLRQRI672
1RWXVHG
6ZLWFKHVWRHQDEOHRUGLVDEOH672
Both switches = ON: STO is enabled
Both switches = OFF: STO is locked
Two switches different: not permissible
Figure 4-24
Terminals and switches for the "STO" function, frame sizes FSD ... FSG
1. Remove the Control Unit.
2. Connect the cable for selecting STO to terminals STO_A and STO_B.
3. Plug in the Control Unit.
Wiring
4.2 Control interfaces
SINAMICS G120X converter
130
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC