Rated motor voltage
Rated motor current
Rated motor power
Rated motor frequency
Rated motor speed
Motor cooling:
● SELF: Natural cooling
● FORCED: Forced-air cooling
● LIQUID: Liquid cooling
● NO FAN: Without fan
Select the appropriate application:
● VEC STD: In all applications, which do not fit the other setting options.
● PUMP FAN: Applications involving pumps and fans
● SLVC 0HZ: Applications with short ramp-up and ramp-down times.
● PUMP 0HZ: Applications involving pumps and fans with optimized efficiency. The setting
only makes sense for steady-state operation with slow speed changes. We recommend
setting VEC STD if load surges in operation cannot be ruled out.
● V LOAD: Applications with high breakaway torque
Select the control mode:
● VF LIN: U/f control with linear characteristic
● VF LIN F: Flux current control (FCC)
● VF QUAD: U/f control with square-law characteristic
● SPD N EN: Sensorless vector control
3
02792/7
3
027&855
3
02732:
3
027)5(4
3
027530
3
027&22/
3
7(&$33/
3
&75/02'
Commissioning
5.4 Quick commissioning using the BOP-2 operator panel
SINAMICS G120X converter
168
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC