● PWE1, bit 0 … 15: = 0 hex
● PWE2, bit 0 … 15: = 1A hex (26 = 1A hex)
3DUDPHWHUFKDQQHO
3:(KLJKUGZRUG
3:(ORZWKZRUG
,1'QGZRUG
3DJHLQGH[
3DUDPHWHUQXPEHU
6XELQGH[
3DUDPHWHUYDOXHELW
3DUDPHWHUYDOXHELW
3.(VWZRUG
$.
Figure 6-25
Telegram, to activate the automatic restart with p1210 = 26
Write request: Assign digital input 2 with the function ON/OFF1 (p0840[1] = 722.2)
In order to link digital input 2 with ON/OFF1, you must assign parameter p0840[1] (source, ON/
OFF1) the value 722.2 (DI 2). To do this, you must fill the telegram of the parameter channel as
follows:
● PKE, bit 12 … 15 (AK): = 7 hex (change parameter value (field, word))
● PKE, bit 0 … 10 (PNU): = 348 hex (840 = 348 hex, no offset, as 840 < 1999)
● IND, bit 8 … 15 (page index): = 0 hex (offset 0 corresponds to 0 hex)
● IND, bit 0 … 7 (subindex): = 1 hex (command data set CDS1 = index1)
● PWE1, bit 0 … 15: = 2D2 hex (722 = 2D2 hex)
● PWE2, bit 10 … 15: = 3f hex (drive object - for SINAMICS G120 always 63 = 3f hex)
● PWE2, bit 0 … 9: = 2 hex (index or bit number of the parameter: DI 2 = r0722.2)
3DUDPHWHUFKDQQHO
3:(KLJKUGZRUG
3:(ORZWKZRUG
,1'QGZRUG
3DJHLQGH[
3DUDPHWHUQXPEHU
6XELQGH[
3DUDPHWHUYDOXH
3.(VWZRUG
'ULYH2EMHFW
,QGH[
$.
Figure 6-26
Telegram, to assign DI 2 with ON/OFF1
6.3.7
Drive control via BACnet MS/TP
6.3.7.1
BACnet properties
Function description
In BACnet, components and systems are considered to be black boxes which contain a number
of objects. BACnet objects only stipulate the behavior outside the device, BACnet sets no
internal functions.
A range of object types and their instances represent one component.
Each BACnet device has precisely one BACnet device object. An NSAP (Network Service
Access Point - comprising network number and MAC address; MAC: Medium Access Control)
uniquely identifies a BACnet device. This address is BACnet-specific and must not be confused
with the Ethernet MAC address.