6.3.7.3
Setting the address
Function description
Procedure
1. Using parameter p2021, set the address using an operator panel or SINAMICS G120 Smart
Access.
Permissible addresses: 0 … 127.
2. Switch off the converter power supply.
3. Wait until all LEDs on the converter are dark.
4. Switch on the converter power supply again.
Your settings become active after switching on.
You have set the bus address.
❒
Parameters
Parameter
Description
Factory setting
p2021
Fieldbus interface address
0
Advanced commissioning
6.3 Drive control
SINAMICS G120X converter
276
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC