r4022.0...3
CO/BO: PM330 digital inputs status / PM330 DI status
G120X_DP (PM330),
G120X_PN (PM330),
G120X_USS (PM330)
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the status of the digital inputs of the PM330 power unit.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
DI 0 (X9.3, external alarm)
High
Low
-
01
DI 1 (X9.4, external fault)
High
Low
-
02
DI 2 (X9.5, Emergency Off category 0)
High
Low
-
03
DI 3 (X9.6, Emergency Off category 1)
High
Low
-
Dependency:
See also: r4023
Note
DI: Digital Input
r4023.0...3
CO/BO: PM330 digital inputs status inverted / PM330 DI stat inv
G120X_DP (PM330),
G120X_PN (PM330),
G120X_USS (PM330)
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the inverted status of the digital inputs of Power Module 330 (PM330).
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
DI 0 (X9.3, external alarm)
High
Low
-
01
DI 1 (X9.4, external fault)
High
Low
-
02
DI 2 (X9.5, Emergency Off category 0)
High
Low
-
03
DI 3 (X9.6, Emergency Off category 1)
High
Low
-
Dependency:
See also: r4022
Note
DI: Digital Input
r4047
PM330 digital outputs status / PM330 DO status
G120X_DP (PM330),
G120X_PN (PM330),
G120X_USS (PM330)
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the status of the digital outputs of Power Module 330 (PM330).
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
DO 0 (X9.8: enable signal UDC link charged)
High
Low
-
01
DO 1 (X9.11/X9.12: main contactor control)
High
Low
-
Note
DO: Digital Output
Parameters
7.2 Parameter list
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
853