Number
Name
Factory setting
r2225
CO/BO: Technology controller fixed value selection status
word
- %
r2229
Technology controller number actual
-
Table 6-91
PID technology controller, fixed values (direct selection)
Number
Name
Factory setting
p2216[D]
Technology controller fixed value selection method
1
p2220[C]
BI: Technology controller fixed value selection bit 0
0
p2221[C]
BI: Technology controller fixed value selection bit 1
0
p2222[C]
BI: Technology controller fixed value selection bit 2
0
p2223[C]
BI: Technology controller fixed value selection bit 3
0
r2224
CO: Technology controller fixed value active
- %
r2225
CO/BO: Technology controller fixed value selection status
word
- %
r2229
Technology controller number actual
-
Table 6-92
PID technology controller, motorized potentiometer
Number
Name
Factory setting
r2231
Technology controller motorized potentiometer setpoint
memory
- %
p2235[C]
BI: Technology controller motorized potentiometer, setpoint,
raise
0
p2236[C]
BI: Technology controller motorized potentiometer, setpoint,
lower
0
p2237[D]
Technology controller motorized potentiometer maximum
value
100%
p2238[D]
Technology controller motorized potentiometer minimum val‐
ue
-100 %
p2240[D]
Technology controller motorized potentiometer start value
0%
r2245
CO: Technology controller motorized potentiometer, setpoint
before RFG
- %
p2247[D]
Technology controller motorized potentiometer ramp-up time 10 s
p2248[D]
Technology controller motorized potentiometer ramp-down
time
10 s
r2250
CO: Technology controller motorized potentiometer, setpoint
after RFG
- %
Further information
You will find additional information on the following PID controller components in the Internet at:
● Setpoint input: Analog value or fixed setpoint
● Setpoint channel: Scaling, ramp-function generator and filter
Advanced commissioning
6.6 Technology controller
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC
359