Table 6-35
Instance Attribute
No.
Service
Type
Name
Value/explanation
2
get, set
UINT16
Commissioning
state
p0010
3
get
INT16
Motor Type
p0300
6
get, set
REAL
Rated Current
p0305
7
get, set
REAL
Rated Voltage
p0304
8
get, set
REAL
Rated Power
p0307
9
get, set
REAL
Rated Frequency p0310
10
get, set
REAL
Rated Tempera‐
ture
p0605
11
get, set
REAL
Max Speed
p0322
12
get, set
UINT16
Pole pair number p0314
13
get, set
REAL
Torque Constant p0316
14
get, set
REAL
Inertia
p0341
15
get, set
REAL
Base Speed
p0311
19
get, set
REAL
Cos Phi
p0308
TCP/IP Interface Object, Instance Number: F5 hex
Supported services
Class
● Get Attribute all
● Get Attribute single
Instance ● Get Attribute all
● Get Attribute single
● Set Attribute single
Table 6-36
Class Attribute
No.
Service
Type
Name
1
get
UINT16
Revision
2
get
UINT16
Max Instance
3
get
UINT16
Num of Instances
Table 6-37
Instance Attribute
No.
Service
Type
Name
Value/explanation
1
get
UNIT32
Status
Fixed value: 1 hex
1: Configuration acknowledged, by DHCP or saved
values
2
get
UNIT32
Configuration Ca‐
pability
Fixed value: 94 hex
4 hex: DHCP supported,
10 hex: Configuration can be adjusted,
80 hex: ACD-capable
Advanced commissioning
6.3 Drive control
SINAMICS G120X converter
236
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC