Description
WARNING
Electric shock due to interrupted protective conductor
The drive components conduct a high leakage current via the protective conductor. Touching
conductive parts when the protective conductor is interrupted can result in death or serious
injury.
● Observe the minimum cross-section of the protective conductor.
/
/
/
3(
①
Protective conductor for line feeder cables
②
Protective conductor for converter line feeder cables
③
Protective conductor between PE and the control cabinet
④
Protective conductor for motor feeder cables
The minimum cross-section of the protective conductor
①
…
④
depends on the cross-section
of the line or motor feeder cable:
● Line or motor feeder cable ≤ 16 mm
2
⇒ Minimum cross-section of the protective conductor = cross-section of the line or motor
feeder cable
● 16 mm² < line or motor feeder cable ≤ 35 mm
2
⇒ Minimum cross-section of the protective conductor = 16 mm
2
● Line or motor feeder cable > 35 mm
2
⇒ Minimum cross-section of the protective conductor = ½ cross-section of the line or motor
feeder cable
Wiring
4.1 Line supply and motor
SINAMICS G120X converter
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC