Note
For parallel circuit configurations, the parameter index is assigned to a power unit.
r0204[0...n]
Power unit hardware properties / PU HW property
Access level: 3
Calculated: -
Data type: Unsigned32
Can be changed: -
Scaling: -
Dynamic index: PDS, p0120
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the properties supported by the power unit hardware.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
01
RFI filter available
Yes
No
-
07
F3E regenerative feedback into the line supply
Yes
No
-
08
Internal Braking Module
Yes
No
-
12
Safe Brake Control (SBC) supported
No
Yes
-
14
Internal LC output filter
Yes
No
-
15
Line voltage
1-phase
3-phase
-
p0205
Power unit application / PU application
Access level: 1
Calculated: -
Data type: Integer16
Can be changed: C2(1, 2)
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
7
Factory setting:
0
Description:
The duty cycles can be overloaded provided that the drive converter is operated with its base load current before and
after the overload. This is based on a load duty cycle of 300 s.
Value:
0:
Load duty cycle with high overload for vector drives
1:
Load duty cycle with low overload for vector drives
6:
S1 duty cycle (for internal use)
7:
S6 duty cycle (for internal use)
Dependency:
See also: r3996
NOTICE
The parameter value is not reset when the factory setting is restored (see p0010 = 30, p0970).
When the power unit use is changed, short-term communication interruptions may occur.
Note
When the parameter is changed, all of the motor parameters (p0305 ... p0311), the technological application (p0500)
and the control mode (p1300) are pre-assigned according to the selected application. The parameter has no influence
when calculating the thermal overload.
p0205 can only be changed to the settings that are saved in the power unit EEPROM.
p0205
Power unit application / PU application
G120X_DP (PM330),
G120X_PN (PM330),
G120X_USS (PM330)
Access level: 1
Calculated: -
Data type: Integer16
Can be changed: C2(1, 2)
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
0
Max:
1
Factory setting:
1
Description:
The duty cycles can be overloaded provided that the drive converter is operated with its base load current before and
after the overload. This is based on a load duty cycle of 300 s.
Value:
0:
Load duty cycle with high overload for vector drives
Parameters
7.2 Parameter list
SINAMICS G120X converter
502
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC