Note
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
p2031
Fieldbus interface MODBUS parity / Modbus parity
G120X_USS
Access level: 2
Calculated: -
Data type: Integer16
Can be changed: T
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: 9310
Min:
0
Max:
2
Factory setting:
2
Description:
Sets the parity for the Modbus protocol (p2030 = 2).
Value:
0:
No parity
1:
Odd parity
2:
Even parity
Note
Fieldbus IF: Fieldbus interface
Changes only become effective after POWER ON.
The parameter is not influenced by setting the factory setting.
The parameter is set to the factory setting when the protocol is reselected (p2030 = 2).
r2032
Master control control word effective / PcCtrl STW eff
Access level: 3
Calculated: -
Data type: Unsigned16
Can be changed: -
Scaling: -
Dynamic index: -
Unit group: -
Unit selection: -
Function diagram: -
Min:
-
Max:
-
Factory setting:
-
Description:
Displays the effective control word 1 (STW1) of the drive for the master control.
Bit field:
Bit
Signal name
1 signal
0 signal
FP
00
ON/OFF1
Yes
No
-
01
OC / OFF2
Yes
No
-
02
OC / OFF3
Yes
No
-
03
Enable operation
Yes
No
-
04
Enable ramp-function generator
Yes
No
-
05
Start ramp-function generator
Yes
No
-
06
Enable speed setpoint
Yes
No
-
07
Acknowledge fault
Yes
No
-
08
Jog bit 0
Yes
No
3030
09
Jog bit 1
Yes
No
3030
10
Master control by PLC
Yes
No
-
NOTICE
The master control only influences control word 1 and speed setpoint 1. Other control word/setpoints can be
transferred from another automation device.
Note
OC: Operating condition
Parameters
7.2 Parameter list
SINAMICS G120X converter
742
Operating Instructions, 06/2019, FW V1.01, A5E44751209B AC